![]() Suction pressure was -35 degrees C, ambient teperatures were 38 degrees C, and condensing pressure was at 52 degees C. The compressor ran fine until it reached -17 degrees then struggled to hold that temperature. I performed acid tests for the oil, no acid was present, tripple vacced the system and charged with R404A. Upon connection of the Tecumseh Compressor I noticed the Phase Rotation was incorrect(for the Copeland Scroll). ![]() I changed from the Copeland to the Tecumseh as the Copeland had been running inefficiently. ![]() Hey guys, wondering if I could get some advice about a situation I have at the moment.I have a tecumseh 3 Phase recipricating Compressor Model Tagp2516z which was a replacement for a Copeland Scroll Model ZF13K-TSV-556.
0 Comments